The Nextronic DNS-CVA series provides a fully

integrated Voice Alarm system solution, and is

specifically designed to comply with the life safety evacuation requirements of BS 5839 pt 8.


The centralized system is housed in a 19'' racking

cabinet and comprises of a number of DNS-CVA

modules and a power supply. The DNS-CVA module provides all the audio control, monitoring and dual circuit amplification for a single Fire Zone. The power supply provides the main DC, battery backup and charging for the system. Cabinet construction is specific to each

project, but generally comprises of a 37U floor standing rack with a lockable glazed door, and wired in flexible conduit.


The system arrangement is of very high integrity since each Fire Zone essentially has it's own VA system. A

serial data link between modules, enables global

control, and ensures synchronization between modules.


The configuration allows full multi-path audio, for phased evacuation. Any audio source, such as microphones, messages or background music, may be broadcast simultaneously to any combination of zones.

Typical Nextronic VA Control Cabinet

Centralized Voice Evacuation Systems

Nextronic

Nextronic Ltd

Industrial & Commercial Audio Systems       

FEATURES

  • Easy to specify, install and maintain

  • Full compliance with BS 5839 pt 8 and BS EN 60849

  • Easily expandable on site for extra zones or increased circuit loading

  • High Efficiency  Class 'D' Amplifiers

  • Fully software configurable

  • Clear Digital Message playback, upto 4 channels

  • End of Line monitoring suited to all Loudspeaker types

  • Code-locked Keypad for module control and configuration

  • LCD System Status Display and

Product Information

Ref. P40330

AMPLIFIER OPTIONS

Power Amplifiers are integrated within each DNS module and are rated at:

  • Dual 40w

  • Dual 120w

  • Dual 200w

  • Other options available

Nextronic DNS-CVA4040 Amplifier & Controller

Typical Parts required for a Voice Alarm System



DNS-CVA

Module


End Of Line Unit

100v Line Loudspeakers

Power Supply

Battery Backup & Charger

Fire Microphone

Fire Detection Panel (by others)

TYPICAL MULTI-ZONE SYSTEM ARRANGEMENT

Music Source

End Of Line Unit

Network

connection to further

DNS Modules

End Of Line Unit

End Of Line Unit

DNS-CVA

Module


End Of Line Unit

End Of Line Unit

DNS-CVA

Module


Management

Microphone

CENTRAL CABINET

ZONE 1a

ZONE 1b

ZONE 2a

ZONE 2b

ZONE 3a

ZONE 3b

Central Equipment

  • Central Equipment Cabinet 19''rack with lockable glazed door, sized to suit (or can be wall-box )

  • DNS-CVA Modules   VA Control and Amplifier modules (Qty 1 per dual cct VA Zone)

  • Power Supply   Mains /DC battery backup for 24hr standby + 1/2 hr broadcast


Externally Connected Equipment

  • Fire Microphone   Zone selective or Global broadcast, with Evacuate message selection

  • Management Microphone  Zone selective, with General message selection

  • Background Music Source optional CD /Tape /Tuner /etc (may be built into rack)


Field Equipment

  • Ceiling Loudspeakers  suited for office/ corridor/ areas with ceiling tiles

  • Cabinet Loudspeakers  suited for wall mounted locations

  • Horn Loudspeakers  suited for plant-rooms / noisy areas / external areas /

  • Projector Loudspeakers  suited for wall mounting in larger areas

  • Spherical Loudspeakers  suited for hanging from high ceilings in large areas / warehouse / factory

  • Flashing Beacons   for noisy areas where loudspeakers may not be audible

  • End of Line Monitor Units  fitted at the furthest point of each speaker circuit, for monitoring open or       short circuit faults.

Voice Alarm System layout

Nextronic Ltd has a policy of continual improvement, and as such, specifications may change without notice.

Phone: 01949 20010

Fax: 0871 9943484
Email: sales@nextronics.co.uk

Low Voltage Directive

73/23/EEC  (amended 93/68/EEC)

EMC Directive

89/336/EEC (amended 92/31/EEC and 93/68/EEC)

Nextronic Ltd